TROVIS Modbus Proxy for TROVIS-VIEW and SAMSON Controllers

The TROVIS Modbus Proxy is a self-hosted Modbus Proxy for reliable communication between SAMSON TROVIS-VIEW and TROVIS heating controllers, including the SAMSON TROVIS 5573-1xxx series. It provides a stable Modbus TCP endpoint for TROVIS-VIEW and connects to the controller through Modbus TCP, RTU-over-TCP, or Serial RTU.

TROVIS-VIEW → Modbus TCP → TROVIS Modbus Proxy → Modbus TCP / RTU-over-TCP / Serial RTU → controller

The Modbus Proxy forwards Modbus PDUs unchanged and has no controller- or firmware-specific address translation. The TROVIS 5573-1 FW 3.09 code in src/trovis_manager/ remains a separate, read-only integration and research harness; it is not part of the Modbus Proxy core.

Key features

  • Reliable TROVIS-VIEW access through a stable Modbus TCP listener on port 7112.
  • Stable controller firmware upgrades through TROVIS-VIEW using the same reliable proxy connection.
  • Controller connections via Modbus TCP, transparent RTU-over-TCP, or Serial RTU.
  • Docker Compose deployment for Linux servers and NAS systems such as Synology.
  • Persistent controller profiles with a responsive browser-based administration interface.
  • Multi-client sequence arbitration, safe read retries, protected writes, pacing, and proactive reconnects.
  • Transparent operation with USR serial-to-Ethernet adapters in protocol mode None.
  • Controller-neutral Modbus Proxy core without hard-coded register maps or synthetic values.

Why this Modbus Proxy

I use TROVIS-VIEW with Modbus protocol to manage the configuration of my SAMSON TROVIS 5573-1xxx heating controller. However, using my USR-TCP232-E2 modbus adapter's ModbusTCP mode did not provide a reliable connection. It caused unstable communication causing failed reads and writes. Similar problems may also occur with other serial-to-Ethernet adapters that perform their own Modbus TCP-to-RTU conversion.

The reliable setup is to configure the USR adapter as a TCP Server with its protocol mode set to None, and then select RTU-over-TCP in the Modbus Proxy controller profile. This keeps the adapter transparent and lets the Modbus Proxy handle the Modbus TCP-to-RTU framing.

This interoperability problem was the original motivation for developing the TROVIS Modbus Proxy. The project has since evolved into a more general communication layer with several additional strengths:

  • Coordinated multi-client access: TROVIS-VIEW, Node-RED, TROVIS 55 Pro, and other Modbus TCP clients can access the same controller through one Modbus Proxy. Client request sequences are queued and kept together to prevent competing applications from causing failed controller reads.
  • Stable firmware upgrades: With the adapter in transparent None mode and the Modbus Proxy using RTU-over-TCP, serial Modbus RTU frames are transported without being decoded or rewritten by the adapter. Their Modbus PDU payloads remain unchanged, avoiding adapter-side protocol conversion and providing a stable path for TROVIS-VIEW firmware upgrades.
  • Transparent protocol handling: Modbus function codes, addresses, and values are forwarded unchanged. The Modbus Proxy does not depend on a controller-specific register map or synthetic address translation.
  • Flexible controller connections: The upstream connection can use Modbus TCP, transparent RTU-over-TCP, or Serial RTU.
  • Reliable connection management: Configurable pacing, timeouts, safe read retries, and proactive reconnection help stabilize communication with controllers and Ethernet adapters.
  • Protected write operations: Writes are never repeated after an ambiguous result, reducing the risk of unintended configuration changes.
  • Simple self-hosted operation: Docker Compose deployment, persistent configuration, and a browser-based administration interface make the Modbus Proxy suitable for NAS systems and other always-on Linux hosts.
  • Operational visibility: The status interface shows connected clients, queued requests, retries, timeouts, reconnects, and the active controller connection.

Modbus Proxy status

TROVIS Modbus Proxy status dashboard for TROVIS-VIEW and a SAMSON controller

Status overview for the TROVIS-VIEW listener and the active upstream controller connection.

Controller connection

TROVIS Modbus Proxy RTU-over-TCP controller profile

Controller profile using RTU-over-TCP with its target, Modbus unit ID, and access settings.

Private network addresses are redacted in both interface examples.

USR adapter configured for transparent RTU-over-TCP operation

USR adapter example: Socket A uses TCP Server, protocol mode None, and local port 7112.

Quick start with Docker or Python

Docker Compose with the latest Docker Hub image (recommended)

The public multi-platform image supports Linux AMD64 and ARM64. Docker selects the correct image automatically.

mkdir -p data
sudo chown -R 1000:1000 data
docker compose pull
docker compose up -d

Open http://localhost:8083/. The standard compose.yaml pulls docker.io/macsobeck/trovis-proxy:latest; it does not build the repository's Dockerfile and requires no registry login. The container runs with UID/GID 1000:1000 and publishes the TROVIS-VIEW listener on port 7112.

Native Python

Python 3.12 or newer is required.

python3.12 -m venv .venv
source .venv/bin/activate
python -m pip install -e '.[dev,serial]'
mkdir -p data
trovis-gateway --listen-host 0.0.0.0 --listen-port 7112 \
  --admin-host 127.0.0.1 --admin-port 8080 \
  --config-path ./data/config.json

Open http://127.0.0.1:8080/ for a native installation.

Create a controller profile, test its transport connection, and activate it. The connection test opens only the configured transport; it sends no invented Modbus register request. Listener address and port are infrastructure settings supplied by environment variables or CLI arguments, not controller-profile fields.

Profile data persists in the host directory ./data and appears as /data/config.json in the Docker container with mode 0600. A stored access key is masked in the API and UI and is not logged, exposed as a metric, or injected into protocol traffic.

Installation guide

Follow the step-by-step installation guide for:

  • Docker and Docker Compose prerequisites;
  • Synology NAS deployment, bind mounts, UID/GID ownership, and persistent storage;
  • controller profiles for Modbus TCP, RTU-over-TCP, and Serial RTU;
  • USR serial-to-Ethernet adapter settings;
  • TROVIS-VIEW network configuration;
  • upgrades, backups, diagnostics, and troubleshooting.

Safety model

  • Downstream Unit IDs are recorded and restored in responses; the active profile's Unit ID is used upstream.
  • FC01–04 reads may retry after a clear transport failure.
  • FC05/06/0F/10 writes never retry after an ambiguous result.
  • Unknown and vendor-specific function codes are forwarded opaquely and are traceable.
  • All Modbus PDUs, including FC01 addresses, are forwarded unchanged.
  • TCP connections are renewed after 25 seconds by default, before the observed 30-second controller session boundary; renewal occurs before a request and never retries an ambiguous write.
  • All requests to a controller are serialized and paced. Consecutive requests from one connected client retain short-lived affinity so another client cannot interleave a polling sequence.

See Modbus Proxy architecture, configuration, and protocol safety.

Frequently asked questions

Does this Modbus Proxy replace TROVIS-VIEW?

No. TROVIS-VIEW remains the configuration application. The Modbus Proxy provides a reliable network path between TROVIS-VIEW and the heating controller.

Which TROVIS controllers are supported?

The Modbus Proxy core is controller-neutral and forwards Modbus PDUs transparently. The documented deployment has been validated with a SAMSON TROVIS 5573-1xxx controller. Other controllers can be used when they expose a compatible Modbus TCP, RTU-over-TCP, or Serial RTU interface.

Can the TROVIS Modbus Proxy run on a Synology NAS?

Yes. The Docker Compose setup supports NAS deployment, UID/GID mapping, automatic restarts, and a persistent bind-mounted ./data directory for controller profiles.

Which mode should a USR Ethernet adapter use?

Use TCP Server with protocol mode None, then select RTU-over-TCP in the Modbus Proxy profile. Do not enable the adapter's ModbusTCP conversion mode for TROVIS-VIEW communication.

Development assistance

This repository was developed and is maintained by macsobeck with assistance from OpenAI Codex for code analysis, implementation, testing, documentation, and release preparation. All changes are reviewed and published by the repository maintainer.

Development

pytest
ruff check .
git diff --check

The default suite uses only local fake servers and never requires real hardware. The legacy research CLI remains available as trovisctl; its hardware workflow stays read-only. See hardware validation before connecting it to a controller.

Repository layout

  • src/trovis_gateway/: generic Modbus Proxy, transports, configuration, API, and admin UI.
  • src/trovis_manager/: device-specific read-only integration harness.
  • tests/gateway/, tests/unit/, tests/integration/: automated coverage.
  • reference/: immutable source artifacts and derived FW 3.09 research data.
  • docs/: architecture, safety evidence, and research findings.